This Ground Breaking NEC Update Has Everyone Talking (Don't get left behind)

Brendan Lamothe

Key Takeaways

  • The NEC now permits branch circuits with a minimum rating of 10 amps.
  • Potential cost savings could be achieved with smaller wire sizes and breakers.
  • Market availability of materials still lags behind the code change.

Overview of NEC Code Updates

Historical Ampacity Requirements

Until the 2023 update, the National Electrical Code (NEC) recognized a minimum branch circuit size of 15 amps for power and lighting loads. According to Section 210.18 of the 2020 NEC, circuits were rated based on the maximum permitted amperage of the overcurrent device, with specified ratings of 15, 20, 30, 40, and 50 amps. It's important to note that even if you used higher ampacity conductors like 12 gauge or 10 gauge wire with a 15-amp circuit breaker, the circuit's ampacity would still be recognized as 15 amps.

Changes in the 2023 NEC Update

The 2023 NEC introduced a significant change to Section 210.18. Now, 10-amp circuits are recognized, marking a departure from the minimum 15-amp requirement seen in previous codes. An important exception is that 10-amp branch circuits cannot supply receptacle outlets, so they are primarily used for specific applications like LED lighting that demands less power. While cost savings might be anticipated by using smaller 16-gauge wire and 10-amp breakers, practical constraints exist. Currently, manufacturers haven't caught up with the production of 16-gauge NM cable or 16-gauge Romex for power circuits, and 16 and 18-gauge wires in table 310.16 aren't permitted as branch circuit wiring in certain conditions.

Implications for the Electrical Industry

Impact on Manufacturers

The recent change to the 2023 National Electrical Code, particularly in article 210.18, has significant implications for electrical manufacturers. With the minimum branch circuit rating now lowered to 10 amps, there's a potential shift in the production landscape. Manufacturers might need to innovate and start developing products compatible with these new standards.

Currently, the availability of 10-amp circuit breakers and compatible materials is limited. This change signals a potential demand increase for 10-amp rated equipment. However, the cost factor remains a concern. While 10-amp breakers exist, they're not as common as their 15-amp counterparts and may come at a higher price.

The manufacturing sector could consider investing in the development of 16-gauge cable for power circuits. This innovation would be essential for embracing cost-saving measures the code change offers. The challenge lies in catching up with the demand and making these products both efficient and cost-effective to encourage widespread adoption.

The change is arguably a response to the increased use of energy-efficient LED lighting, which requires less power. Manufacturers have an opportunity to leverage this trend and develop solutions that cater to this evolving landscape. You might see new product lines and a shift in production priorities addressing these changes as the industry adapts over time.

Analyzing the Code Change

Understanding Branch Circuit Ratings

The code update in the 2023 NEC for Article 210.18 introduces a notable change to branch circuit ratings. Previously, the smallest branch circuit recognized for power and lighting loads was 15 amps. Now, the code allows for circuits as small as 10 amps. It's crucial to note that the circuit amp rating is based on the circuit breaker's rating, rather than the wire size. For instance, you can run 10-gauge wire with a 15-amp circuit breaker, and the circuit ampacity remains at 15 amps.

In this context, a key element of the 2023 change is the introduction of 10-amp circuits. This is seen as a response to the evolving electrical demands related to energy-efficient lighting solutions, like LEDs, which require less power. Despite these changes, the practical implementation might face hurdles until relevant products become more available.

Specifics of the 10 Amp Inclusion

The permission for 10-amp circuits comes with certain restrictions. For example, there’s a new exception which states that 10-amp rated branch circuits cannot supply receptacle outlets, meaning traditional outlets still need circuits rated at no less than 15 amps.

While 10-amp breakers can be purchased, they aren't as commonly available as 15-amp breakers and might cost more at present. The addition of 10-amp circuits carries potential cost savings due to reduced wire size, yet currently, there's no widespread production of suitable 16-gauge cables for these circuits. You might find 16-gauge wire for running in raceways like EMT, but they can't legally be used as branch circuit wiring as outlined in the updated code. As manufacturers catch up, the practical application and financial benefits may improve, making them a feasible option in the future.

Advantages and Challenges

Potential Cost Savings

Switching to 10 amp branch circuits provides a clear pathway to potential cost reductions. Reducing wire size to 16 gauge and installing 10 amp breakers are expected to cut down on material costs, providing some savings on labor as well. The cost-effectiveness is not only tied to materials but also labor efficiency with using smaller components.

Current Availability of Components

At present, 10 amp circuit breakers can be purchased, though they remain uncommon. This rarity means prices are slightly higher compared to the more standard 15 amp circuit breakers. Additionally, while you can find 16 gauge wire, its application in certain power circuits is limited since there's no 16 gauge NM cable readily available for current standard uses.

Regulatory Compliance Issues

Compliance presents a challenge, as shown by the new exception in the revised code which specifies that 10 amp branch circuits cannot supply receptacle outlets. As a result, while the allowance for 10 amp circuits exists, certain applications remain restricted, ensuring adherence to safety and performance standards.

Practical Considerations

Waiting for Industry Adaptation

As you navigate the 2023 National Electrical Code changes, you'll encounter the introduction of 10 amp branch circuits in article 210.18. While this seems promising with the potential for cost savings due to smaller wire sizes, the reality is a bit more nuanced.

First, consider the availability of materials. Currently, manufacturers have not widely produced 16 gauge Romex or NM cables for power circuits. This limitation impacts your ability to fully implement 10 amp circuits. Sure, you can find 10 amp circuit breakers, but they are still uncommon and might even cost more than the standard 15 amp breakers.

If you're thinking about utilizing EMT raceways, keep in mind that despite being able to run 16 gauge wire, circuit usage restrictions apply. The current tables and regulations in the NEC limit feasibility for these installations, rendering this approach impractical for now.

While the potential benefits are enticing, the electrical industry needs time to adapt. As manufacturers begin to catch up with these changes, it's essential to remain patient and informed. You might eventually see financial advantages once products become available and regulations adjust.

Until then, it's wise to continue using existing standards and materials that align with the proven 15 amp circuits.

Conclusion

The 2023 update to the National Electrical Code (NEC) introduces a compelling change to Article 210.18, now allowing for branch circuits as low as 10 amps. Previously, the smallest recognized was 15 amps. Significantly, this shift is seen as a response to the increased use of energy-efficient LED lighting, which demands less power.

There are considerations to bear in mind. Notably, 10 amp circuits cannot supply receptacle outlets, maintaining the requirement for a minimum of 15 amps. Cost savings are possible through the use of 16-gauge wire and 10 amp breakers, though availability is currently limited as 16 gauge ROMEX or NM cable is not yet available for power circuits.

While 16 and 18 gauge wires appear in the NEC Table 310.16, their use for branch circuit wiring is restricted, specifically in the 90° columns, thus presenting another challenge in implementing this code change immediately.

For now, it's a matter of waiting for manufacturers to produce suitable materials that could make these cost-saving changes feasible.